At Winterhaven, a battery’s value during an outage depends on the condition of the lines connecting it to the load.

Published November 20, 2026Intelligence / Energy / Advanced Battery Tech

When wind broke 68 power poles near Winterhaven and Bard in August 2022, the Imperial Irrigation District restored most of its affected customers by switching lines and isolating damage. Eighteen hours after the storm, 44 of the original 853 customers were still without service. By then the essential difference between the two groups was whether crews could get electricity to them. Putting more energy at the head of a broken line would have done little for the people at its far end.

The district and CMBlu now propose a long-duration battery at the Pilot Knob hydroelectric plant on the Fort Yuma Indian Reservation. The November 18 state vote paid particular attention to the small end of the announcement. The California Energy Commission voted 4–0 to approve a $7,111,984 grant agreement and directed staff to execute it. The first installation is rated for one megawatt of power and ten megawatt-hours of stored energy. The larger Echo Sands proposal, 10 MW and 100 MWh, is ten times the size at exactly the same duration. Only the first installation is in the grant scope.

CMBlu combines circulating electrolyte, which carries charge through the electrochemical cells, with solid material for storage. The design lets engineers size the power-conversion equipment separately from the inventory that holds energy. Ten MWh could in principle serve a steady half-megawatt load for 20 hours. A group of pumps that all start at once could exceed the one-megawatt rating while the store is still nearly full. The energy left when an outage starts, conversion losses and operating reserves all affect the result at the customer meter.

For a damaged grid, a further piece of engineering stands between the battery and a light that comes back on. Operators have to isolate a safe, intact section of circuit, establish its voltage and frequency, and reconnect loads in an order the source can support. The Department of Energy illustrates the sequence in a microgrid demonstration: open the connection to the failed system, energize an intact feeder, then bring loads and other generating equipment back in stages. That example explains what the district would have to demonstrate for a particular feeder. It supplies no evidence that Pilot Knob can already do so.

The grant work plan calls for operating baselines and annual technical, economic and performance assessments. The sharpest comparison will be with what the district already accomplished using switches in 2022. During a similar fault, which additional loads could the battery reach, for how long, and which would still wait for a line crew? A successful test might keep one critical pump running through an entire repair even if its effect on the total number of outages looked small. That is a valuable outcome the ten-hour nameplate cannot convey.

Sources. IID storm record · Project announcement · Certified CEC resolution 26-1118-03c · Commission work plan · Department of Energy islanding demonstration.

CMBlu and STRABAG representatives stand beside battery equipment at their 2023 partnership announcement. Courtesy of STRABAG and CMBlu Energy